Low subcool high superheat

A 30-psi pressure difference is usually the minimum across TXVs. This reduced refrigerant flow causes a starved evaporator that will in turn cause low suction pressures and high superheats. However, this may be offset by increased subcooling at low ambients.

Low subcool high superheat. What does high superheat mean? Under charge. What does low superheat mean? Overcharge. What does high subcooling mean? Overcharge. What does low subcool mean. Undercharge. If you wire up to 24 V transformers how do you wire them? In parallel with each other, phasing has to match. If you measure humidity in the air, how do you do that? Wet bulb ...

The limit to any compressor discharge temperature is 225°F. If the discharge temperature gets higher than 225°, the system may start to fail from worn rings, acid formations, and oil breakdown. Remember, if the discharge temperature is 225°, the actual discharge valve will be about 75° hotter. This will bring the actual compressor's ...

A high superheat is an indication of either a low refrigerant charge or a liquid line restriction problem. To tell the difference between the two problems, we look at subcooling. A system with a low refrigerant charge will have a low subcooling. A system with a liquid line restriction will have a normal to high subcooling.Grab the two approximate outdoor temps from the chart, then just use the 2 rows of pressures and temps along with the indoor wet bulb temp. Study with Quizlet and memorize flashcards containing terms like What is the operational range for the superheat and subcool?, When the Superheat is below the operational range, is it overcharged or ...A solid understanding of superheat and subcooling is essential. Troubleshooting often requires simultaneous knowledge of temperature, pressure, voltage, and current values in a system. A single-function meter won't permit a complete analysis of the system. Frequently, multiple tools are required. This article provides information on ...Nov 21, 2023 · Superheat and subcooling data can help you pinpoint these issues quickly. Common Causes of Superheat and Subcooling Imbalance. Common reasons for superheating and subcooling include issues such as liquid line restriction, malfunctioning metering systems, and limited airflow, all of which can lead to high superheating and low subcooling levels. 1. Subcooling degrees are figured by taking the difference between the discharge saturation temperature and the discharge line temperature. The amount of subcooling for optimum operation should be specified by the equipment manufacturer. An overcharged system will have low superheat, potentially allowing liquid refrigerant to damage the compressor.High Subcooling Causes: Low refrigerant charge (undercharged system). Restriction in the liquid line (usually ice). Indoor airflow (CFMs) is too high. Indoor heat load is too high. Metering device (TXV, AEV, or piston) is underfeeding. High refrigerant charge (overcharged system). Restriction in the liquid line (usually ice). Metering device ... If superheat is low and sub-cooling is high: Charge must be adjusted. System overcharged If superheat is high and sub-cooling is high: Could have blockage in coil, orifice or line set. If superheat is low and sub-cooling is low: Orifice could be too big, there is no orifice in the unit of the orifice is stuck and refrigerant is by-passing it.

Low Refrigerant charge: Verify Subcooling (15-20 F) and EXV 40-50% open at full load, 12 F superheat; Ratio= EXV % flow command / Superheat Control Compressor Flow estimate > 1.6; Incorrect Setting of Low refrigerant Temp Cutout (IOM). It should be set for type and percent (%) of glycol concentration ... - Water Flow too low- High concentration ...Master the art of HVAC maintenance with our focused guide on troubleshooting subcooling and superheat issues. Learn to interpret the signs, pinpoint problems, and apply practical solutions for optimal system performance. With clear explanations and actionable advice, this guide is essential for any HVAC professional or enthusiast.Good Subcooling Value for R-410A: Similar to superheat, the ideal subcooling value for R-410A can vary depending on factors like system design and operating conditions. However, a common target for R-410A systems is to achieve a subcooling value in the range of 8 to 15 degrees Fahrenheit (°F) or approximately 4.4 to 8.3 degrees Celsius (°C).Low subcooling and high superheat are both conditions that can occur in a refrigeration system and indicate a problem with the system's balance. Low subcooling means that there is an insufficient amount of refrigerant in the condenser, which is the part of the system where the refrigerant releases the heat it has absorbed from the evaporator. ...To check subcooling, attach a thermometer to the liquid line near the condenser. Take the head pressure and convert it to temperature on a temperature/pressure chart. Subtract the two numbers to get the subcooling. For example, 275 psi head pressure on an R-22 system converts to 124°F. The liquid line temperature is 88°F.One sign of low subcooling is high suction pressure in your HVAC system. When there’s not enough subcooling, the refrigerant pressure in the system can become elevated, which can lead to poor cooling performance and potential damage to your system. Low discharge pressure. Low discharge pressure is another sign of low subcooling.

Normal superheat low subcool . So here's the stats, I have a normal superheat, and low subcool, my coil temp is 42f 130psig on suction side, with suction line temp of 51f And on my high side I have a head pressure 220psig, 74f on the condenser coil temp and the liquid line read at 71f. My delta was around 12 with a 72f return air and 60 ...If you do top it up, make sure the quantity is weighed. This will be a definitive distinction between short or a restriction. The plan is to add some refrigerant to it and see how it responds (funny thing is the one tool I don't have is a scale ). If low side comes up and subcool behaves, then it is a leak.High superheat low subcooling is when there is a limited flow of refrigerant in the evaporator and a limited flow of the refrigerant in the condenser. It is worth noting that in systems with liquid line receivers, subcooling will not increase because the liquid will go to the receiver instead of the condenser although the receive line filter is ...Low Refrigerant charge: Verify Subcooling (15-20 F) and EXV 40-50% open at full load, 12 F superheat; Ratio= EXV % flow command / Superheat Control Compressor Flow estimate > 1.6; Incorrect Setting of Low refrigerant Temp Cutout (IOM). It should be set for type and percent (%) of glycol concentration ... - Water Flow too low- High concentration ...High superheat due to excessive heat load and low subcooling due to poor compression. In practice, more than 95% of issues, when we see high superheat and low subcooling, are caused by a lack of refrigerant (undercharged refrigerant lines). Here’s how to fix that: How To Fix High Superheat Low Subcooling In AC Unit?

Gypsy joker.

Hey my fellow tech. I recieved a call today that the unit was freezing over on a old carrier unit. So i went through the protocol, IDM, Filter, Evap coil, ductwork, all checked out good. Before i continue recommend every tech to go get the testo 550 they're so nice. Anyhow hooked up my testo to the unit the unit and checked my superheat sence it had cap tubes.Many servicemen experience service calls where the compressor has both a low head pressure and a high suction pressure. There are three main reasons why a reciprocating compressor will simultaneously have a low head pressure and a high suction pressure. ... Condenser subcooling: 10 Evaporator superheat: 15 Compressor superheat: 45 Here are some ...4. Low Subcooling Caused Poor Compression (Potential Compressor Problem) 1. Low Refrigerant Charge (Low Subcooling) Or High Refrigerant Charge (High Subcooling) The most common cause for non-normal subcooling is a wrong refrigerant charge. If the system is overcharged (too much freon), we will get high subcooling.In this guide we are going to explain everything you need to know about symptoms of bad TXV and how to properly diagnose it. The symptoms of a bad TXV include high superheat, low superheat, high subcooling, low suction pressure and low head pressure. However you might need to take additional diagnostics steps to rule out other …Rebuilding your credit is a challenge, but it’s possible to start the process by getting a credit card, paying it off regularly and keeping the balance low. This method requires yo...

High side pressure and subcool become the determining factor in charging because of the TXVs ability to change flow rate. Superheat still can be measured though to determine if a TXV is operating properly. Some TXVs can be manually adjusted to change spring pressure and flow rate. ... Low Charge- If refrigerant charge is low, the …Step 4: Measure Initial Superheat. Before making any adjustments to the TXV, you'll need to establish a baseline by measuring the existing superheat. Attach a temperature probe to the suction line near the evaporator coil. Note down the temperature reading. See also Compressor Short Cycling: 6 Proven Solutions.Subcooling is beneficial because it prevents the liquid refrigerant from changing to a gas before it gets to the evaporator. Pressure drops in the liquid piping and vertical risers can reduce the refrigerant pressure to the point where it will boil or "flash" in the liquid line. This change of phase causes the refrigerant to absorb heat before ...The main reasons your compressor will have simultaneously low head pressure and high suction pressure is due to: Bad or leaky compressor valves. Worn compressor piston rings. Leaky oil separator return line. Your compressor valves may become inefficient due to poor sealing from dirt and debris deposits.What causes high superheat and low subcooling? If superheat is high and sub-cooling is high: Could have blockage in coil, orifice or line set. If superheat is low and sub-cooling is low: Orifice could be too big, there is no orifice in the unit of the orifice is stuck and refrigerant is by-passing it.High subcooling is usually accompanied by high head pressure because liquid is displacing available condensing area. Low superheat, low evaporator load - dirty filter, slipping belt, low fan speed, filthy coil. High superheat, evaporators being starved for refrigerant if suction pressure is low. If suction pressure is high and superheat seems ...On the flip side, high superheat might indicate low refrigerant levels or poor airflow across the coil. Again, catching these early helps prevent bigger headaches down the road. So yeah, measuring superheat and subcooling regularly is like giving your HVAC system a longer lease on life.In this guide we are going to explain everything you need to know about symptoms of bad TXV and how to properly diagnose it. The symptoms of a bad TXV include high superheat, low superheat, high subcooling, low suction pressure and low head pressure. However you might need to take additional diagnostics steps to rule out other factors that can ...Superheat = Current Temperature - Boiling Point. Superheat is measured by its temperature above its boiling point. If a refrigerant vapor boiling point is 140 degrees, for example, then anything about that pressure would be too high for that specific refrigerant. To calculate the measurement of subcooling, the formula is: Subcooling = Boiling ...

One sign of low subcooling is high suction pressure in your HVAC system. When there's not enough subcooling, the refrigerant pressure in the system can become elevated, which can lead to poor cooling performance and potential damage to your system. Low discharge pressure. Low discharge pressure is another sign of low subcooling.

High subcooling is usually accompanied by high head pressure because liquid is displacing available condensing area. Low superheat, low evaporator load - dirty filter, slipping belt, low fan speed, filthy coil. High superheat, evaporators being starved for refrigerant if suction pressure is low. If suction pressure is high and superheat seems ...Study with Quizlet and memorize flashcards containing terms like Subcooling is an important process that ensures _______ refrigerant enters the ________., High subcooling means there is how much liquid? Low subcooling means there is how much liquid?, Subcooling can be defined as: and more.PIMCO LOW DURATION CREDIT FUND CLASS I-2- Performance charts including intraday, historical charts and prices and keydata. Indices Commodities Currencies StocksHigh pressures can cause refrigerant leaks at the condenser, leading to high superheat and low subcooling. To avoid these issues, ensure sufficient airflow by keeping condenser coils and fins clean. 2. Malfunctioned Metering Devices. The metering tool controls the refrigerant flow. A malfunctioning tool can result in refrigerant flow ...At low or moderate superheat, nucleate pool boiling heat transfer increases, when the subcooling increase, while it is insensitive to the subcooling, at high superheat. 2. The limit of the convergent zone or the high superheat zone is highly dependent upon the heater. The above conclusions are generally in agreement with that of (11) .If it does it in decent weather: It's airflow. Or, more accurately a lack of heat load on the evap. Your txv has bogged all the way down, creating a high subcool. It's bogged so far down, and still can't maintain a decent superheat. This is from your low evap temp, low sh and high subcool.Nothing indicates plugged filter drier. Your suction pressure is high as fuck, you can't drop the temperature in a 30F Room with 30F saturated suction temperature. If your filter drier was plugged you would have low suction pressure and high superheat. This looks like something is going on internally and stopping your compressor from moving gas.Subcooling The last function of the condenser is to subcool the liquid refrigerant. Subcooling is defined as any sensible heat taken away from 100% saturated liquid. Technically, subcooling is defined as the difference between the measured liquid temperature and the liquid saturation temperature at a given pressure.High superheat AND high subcooling is an indication of a liquid line restriction Low superheat and low subcooling is an indication of an overfeeding metering device NOTE: These are just guidelines and INDICATIONS OF A SYSTEM PROBLEM, since other system problems may result in the appearance of these symtoms.In short, high discharge temp can commonly be caused by: Low charge (high suction superheat, low suction pressure, low subcool) Severe overcharge. Low condenser airflow. Restricted metering devices. Other restrictions (liquid line drier, suction line drier, kinked lines, clogged screens) Low discharge line temp can be caused by.

Pi kappa phi secret handshake.

Hurricane boat decals.

Superheat and Sub-Cooling. Whenever an HVAC technician needs to add refrigerant to a system or adjust the charge the tech needs to know what superheat and/or sub-cooling is to properly ensure the refrigerant charge is correct. It is also important to have a pressure-temperature or PT Chart to properly read the pressures and temperatures.Low superheat high subcooling is a common issue with AC units. There are 5-6 low superheat causes and 3 high subcooling causes. By comparing these causes, we can see which ones are the reason we have low superheat and high subcooling. Here is a chart of low superheat causes (on the left) and high subcooling causes (on the right). The …High discharge pressure, high suction pressure. with high super heat and subcooling; Cookie Consent We use cookies to improve your website experience. ... I have 325psi on the high side and 87psi on the low side. The superheat is 31 degrees and the sub cooling is 40 degrees. It does not have a txv. Reply . 07-27-2011, 09:01 PM #6. hvacjamie.High Subcooling Causes: Low refrigerant charge (undercharged system). Restriction in the liquid line (usually ice). Indoor airflow (CFMs) is too high. Indoor heat load is too high. Metering device (TXV, AEV, or piston) is underfeeding. High refrigerant charge (overcharged system). Restriction in the liquid line (usually ice). Metering device ...Table of Contents. 1. Low Superheat Normal Subcool Caused By Low Indoor CFMs (Dirty Filters Or Coils) 2. Low Superheat Normal Subcooling Caused By Oversized AC Unit. …Adjust the superheat of the valve to a slightly higher value. Attempting to control an evaporator near to or lower than 5°F operating superheat can exceed the sensing capability of most expansion valves and result in hunting and subsequent intermittent flooding. If practical, move the bulb farther downstream on the suction line.Superheat in HVAC refers to the temperature of refrigerant vapor above its saturation point in the evaporator. Ideal superheat is typically 10-15°F. Subcooling involves refrigerant liquid temperature below its saturation point at the condenser outlet. Normal subcooling is often 10-15°F. Both metrics help assess system efficiency and refrigerant state, but acceptable values can vary by ...Attach the Manifold Gauges. Connect the manifold gauges to the low-pressure port. Ensure it is attached securely to prevent any leakages and to get accurate readings. Take Temperature and Pressure Readings. Using a thermometer, take the temperature reading of the suction line — this is the line that carries the refrigerant back to the unit.Once the refrigerant has boiled to a vapor then any temperature above and beyond the boiling point is known as the Superheat. In other words, Superheat is any temperature of a gas that is above the boiling point for that liquid. The reason that Superheat is so important to measure is that it can give you a direct indicator as to what is wrong ... ….

Accurately Measuring Superheat And Subcooling. For example.....Let's say the low pressure curve on a system at an outdoor temperature of 85 degrees dry bulb, indoor wet bulb temperature of 59 degrees shows the suction pressure should be 71 pounds. The saturation temperature (this is an R-22 systems) = 41.7 degrees.Terms in this set (8) find the low side pressure and convert it to the saturation temp. measure the suction line temp with thermometer. Superheat = suction line temp - saturation temp. find the high side pressure and convert it to the saturation (condensing point) temp. measure the liquid line temp. Subcooling = saturation temp - liquid line temp.High superheat, low subcooling—or high subcooling, low superheat—can tell us a story about the system and its needs. Ensuring that a system is fully operational within the appropriate ranges means that you need the right tools …Refrigerant restrictions will be low suction: high superheat, high subcooling. Often once you resolve the charge issue, you may also find another low load issue that contributed to the freezing. In many cases, when a low charge is the main cause, the customer will notice the issue before the system is FROZEN SOLID.What is superheat and Subcool? While superheat indicates how much refrigerant is in the evaporator (high superheat indicates not enough, low superheat indicates too much), subcooling gives an indication of how much refrigerant is in the condenser. Subcooling on systems that use a thermostatic expansion valve (TXV) should be approximately 10F to ...Lowe’s is the second-largest hardware chain store in the country, and one of America’s largest retailers, reports the website The Balance. As of 2018, it had just under 2,400 locat...Basically the title. I am still doing ride alongs and my co worker and I are stumped after installing a unit. It is one of those systems where the…3. 4. 5. (1 Vote) Superheat is the difference between the actual temperature of the refrigerant gas as it leaves the evaporator and the boiling point temperature of the refrigerant in the evaporator coil. After boiling, the refrigerant continues to warm up. The number of degrees it “warmed up†after boiling is called the superheat. Low subcool high superheat, Take the condensing temperature and the condenser outlet temperature, and the difference between the two is the amount of subcooling. “Let’s say the condensing temperature is 100°F. Put a thermistor on the condenser outlet, and let’s say that’s 90°,” continued Tomczyk. “So, you have 10° of subcooling. Technicians get confused ..., Yes, high superheat and low subcooling can harm your HVAC system. High superheat levels can cause the air conditioning system to deliver less cooling. It can also cause the compressor to overheat, potentially damaging it. The same goes for low subcooling., From the Goodman manual for that model. Outside drybulb 95F inside drybulb 80F. Hi pressure = 335 Psig, Lo pressure 130 Psig. Which is 20-30 psi off on both. But I was under the assumption if it where low on 410a there would be high superheat and high subcooling. Like I said I’m new. With the excessive subcooling and no superheat, I am confused., Superheat is usually an indication of low refrigerant charge. Superheat in a car AC system isn't a good thing. Car AC systems work by metering high pressure liquid refrigerant into an evaporator. The current refrigerant R-134a has a boiling point of -15.4°F. It enters the evaporator as a liquid., At low or moderate superheat, nucleate pool boiling heat transfer increases, when the subcooling increase, while it is insensitive to the subcooling, at high superheat. 2. The limit of the convergent zone or the high superheat zone is highly dependent upon the heater. The above conclusions are generally in agreement with that of (11) ., Superheat and subcooling data can help you pinpoint these issues quickly. Common Causes of Superheat and Subcooling Imbalance. Common reasons for superheating and subcooling include issues such as liquid line restriction, malfunctioning metering systems, and limited airflow, all of which can lead to high superheating and low subcooling levels. 1., Freezer superheat and subcooling. Hello HVAC tech I am working on a walk in freezer box temp is -10 degrees. this is a R402A refrigerant unit by Larkin it is a Copeland compressor. My suction temp. at the compressor is 33.7 the saturated temp is -32 at 10 psi. the High side is 215 psi saturated temp 89 degrees and the pipe temp is 91 degrees ..., The service technician would see 22°F of evaporator superheat and 11°F of condenser subcooling. This normal subcooling may lead the technician to believe the system is not undercharged; however, the high evaporator superheat could lead the technician to think that the evaporator is being starved from a TXV out of adjustment., Low superheat and high subcooling occur mainly when the refrigerant charge is high or the faulty metering TVX or AEV device. You can overcome the issue by removing the excess refrigerant charge, repairing the metering device, and cleaning up the condenser coil to avoid any restrictions in the line. , 4. Low Subcooling Caused Poor Compression (Potential Compressor Problem) 1. Low Refrigerant Charge (Low Subcooling) Or High Refrigerant Charge (High Subcooling) The most common cause for non-normal subcooling is a wrong refrigerant charge. If the system is overcharged (too much freon), we will get high subcooling. , 3. Airflow through the evaporator is too high. When there is an excess flow of air through the evaporator coil, the capability of the system to remove moisture is reduced. The vapor picks up more than usual heat which causes the suction pressure to be higher than normal pressure and has a higher superheat. 4., Low subcooling means that a condenser is empty. High subcooling means that a condenser is full. Overfilling a system increases pressure due to the liquid filling of a condenser that shows up as high subcooling. To move the refrigerant from the condenser to the liquid line, it must be pushed down the liquid line to a metering device., Superheat is measured as the difference between the actual temperature of refrigerant vapor at a certain point and the saturation temperature of the refrigerant. It’s not complicated, but for a beginning tech, it might be.”. Superheat may be so complicated just because of the term “heat,” Tomczyk said. “Because something can be minus ..., The high-pressure (HP) setting for R404A can vary depending on the specific refrigeration system and its operating conditions but typically falls between 200 and 250 psi. What is the ideal range of subcooling? The ideal range of subcooling for R404A is generally around 10 to 20 degrees Fahrenheit., Saying you've never had a problem setting charge when if you don't charge by subcool on a txv then you literally didn't properly charge the system. Oh and there is no reason to believe that superheat is low. Even if it was a piston system depending on load conditions 8 superheat is not only perfectly acceptable… it can be required., Then unit need 3.6lb of refrigerant, charged it and pressures were like this: Low side press: 79psi. High side press: 300psi. Suction tube temp: 89ºf. indoor temp: 75º-77ºf. outside temp: 90º. Cause the superheat was high i tough the evap was starving cause a restriction, so i replaced the liquid line filter, blow the lines w/nitrogene ..., ant type used. The difference in temperature is the subcooling value. Note: Condensing temperature is derived from using the PT chart. On new refrigerant blends with high temperature glide, this is called the bubble point (BP) temperature. See Figure 2. To measure subcooling with an 80PK-8 Pipe Clamp, allow the system to run long enough for, High suction pressure. One sign of low subcooling is high suction pressure in your HVAC system. When there’s not enough subcooling, the refrigerant pressure in the system can become elevated, which can lead to poor cooling performance and potential damage to your system. Low discharge pressure. Low discharge pressure is another sign of low ..., Superheat = Current Temperature - Boiling Point. Superheat is measured by its temperature above its boiling point. If a refrigerant vapor boiling point is 140 degrees, for example, then anything about that pressure would be too high for that specific refrigerant. To calculate the measurement of subcooling, the formula is: Subcooling = Boiling ..., High superheat low subcooling on a TXV system means that there is no sufficient amount of refrigerant in the evaporator and there is low amount of the refrigerant in the condenser unit. This condition is mainly caused by low charge in an air conditioning system and can be fixed by sealing leaks and adequately charging the system with a refrigerant., Evaporator Superheat Method: 1. Take the suction line pressure and temperature at the condenser's suction service valve (air conditioning) or service port at the compressor (heat pump). If you use a probe-type thermometer, put a …, High subcooling and normal superheat readings provide valuable insights into the efficiency and functionality of HVAC systems. These diagnostic measures play a crucial role in determining the refrigerant charge and heat transfer processes within the system., 28. Post Likes. high super heat low suction. any ideas. I am working on a ruud heat pump. Freeze up problems. Low suction pressure, 24 superheat, 8 subcooling. 14 degree air drop across my coil. I have evacuated and wieghed in a charge r-22 and replaced txv. No kinks in line set and not a plugged filter dryer. .5 static pressure across my coil., Hello I have a 20 TON AAON Split coil condenser, each compressor is 10 tons. Unit is R410A. Semi annuals have just been done on the unit so all coils and filters are clean. Outdoor air was 93, indoor was 67. Condenser has 2 fans and both are running at proper speed. The high superheat and low subcooling would normally suggest to me that the unit is low on Freon and needs to be charged, but my ..., When it comes to building a deck, you want to make sure you have the best materials available. Lowes is one of the top retailers for decking supplies, offering a wide selection of ..., There are indeed some cases where low suction pressure is going to be caused by low refrigerant. If the superheat is high and the subcooling is low, the refrigerant charge is probably low. Just keep in mind two things here: first, find and fix the leak. Second, monitor both superheat and subcooling as you add the refrigerant, to prevent ..., Low superheat high subcooling is a common issue with AC units. There are 5-6 low superheat causes and 3 high subcooling causes. By comparing these causes, we can see which ones are the reason we have low superheat and high subcooling. Here is a chart of low superheat causes (on the left) and high subcooling causes (on the right). The culprits ..., Jun 24, 2015 ... Comments88 · What's wrong with this air conditioner #3 · AC Troubleshooting Low Superheat · High Suction Pressure Resolved · How to..., Superheat and subcooling data can help you pinpoint these issues quickly. Common Causes of Superheat and Subcooling Imbalance. Common reasons for superheating and subcooling include issues such as liquid line restriction, malfunctioning metering systems, and limited airflow, all of which can lead to high superheating and low subcooling levels. 1., Low subcooling means you won’t have enough liquid refrigerant to feed your expansion valve. High subcooling means you may have to much refrigerant in the system or you have a subcooling circuit in the system that helps subcool the liquid refrigerant more. I’ve seen subcooling circuits on chillers and VRF/VRV systems., New Guest. Join Date. Sep 2012. Posts. 2. Post Likes. How to interpret high Superheat + low subcooling? Hi, every one, I'm new in HVAC, please help me to diagnose my home …, Taking the measurements is useful for any type of system, to identify trouble spots. However, when charging a TXV system, you charge by subcooling. And, when charging a cap-tube system, you charge by superheat. Both types can be charged by weight, if known. Trust, but verify. RSES Certificate Member Specialist., Post Likes. Low subcooling results when there is insufficient refrigerant to fill the lower part of the condenser coil. High suction superheat results when there is insufficient refrigerant to fill the evaporator properly. If you have insufficient refrigerant in both places - it is likely that the system is undercharged.